The classification determines the quantity allowed in a control area, the tank separation distances and the protection requirements. It is the starting point for almost every other calculation involving liquids.

Demonstration scenario

Technical acetone — flash point −17°C, boiling point 56°C

Liquid properties

Flash point (closed cup)From the safety data sheet
−17 °C
Boiling pointRequired for the sub-classification
56 °C
Source of the value
Safety data sheet, section 9
  • The flash point was measured in a closed cup. An open-cup measurement gives a higher value and is not suitable for classification.
  • The 37.8°C boundary between a flammable liquid and a combustible liquid is verified and in our hands — Procedure 27 §3.11–3.12. What is missing is the IA/IB/IC/II/IIIA/IIIB sub-classification split and the boiling point condition, which the procedure refers to in footnotes 25 and 26 (NFPA 30 2024, table 9.6.1).

Result

Classification
Flammable liquid
Sub-classification

Requires the full classification table

Deciding condition
Flash point below 37.8°C

Interface demonstration — not a professional result. The values marked — will be calculated once this tool's data source has been loaded.

Data source

NFPA 30 (2024), chapter 4 — the classification table

The primary boundary is verified from the procedure. The sub-classification split requires the standard itself.

What is blocked, and what would release it

  • NFPA 30 (2024) — table 9.6.1, the sub-classification split

    One specific part is missing, not the whole document. The principal boundary is held and verified: procedure 27 §3.11–3.12 defines a flammable liquid as one with a flash point below 37.8 °C and a combustible liquid as one above it, and appendix ג page 15 carries the class names and their quantities. What the procedure does not carry is the sub-classification split itself — what separates IA from IB from IC, where class II sits, and what separates IIIA from IIIB — together with the boiling point condition that divides the lowest band. The procedure points there explicitly: footnotes 25 and 26 on page 15 attribute the values to NFPA 30 (2024), tables 9.6.1 and 18.5.4.

    We currently have no legitimate route to obtain the document.

Until the source is obtained, the tool shows the interface and the calculation steps, and presents no regulatory value.

Your data is stored in this browser alone and is never sent to Hoshen or to anyone else.